Refrigeration cycle multi-tool for DX air coolers and chillers, air- or water-cooled, with heat recovery. Properties from CoolProp
| Point | p bar abs | t °C | h kJ/kg | s kJ/kgK |
|---|
Properties: CoolProp 8.0 (IIR reference state, h = 200 kJ/kg and s = 1 kJ/kgK for saturated liquid at 0 °C; R717 uses its own reference state), stored as tables and interpolated in ln p and superheat. Subcooled liquid is approximated with the enthalpy of saturated liquid at the same temperature. For zeotropic blends (R407C, R404A), superheat refers to the dew line and subcooling to the bubble line. Secondary side: water capacity Q = V·ρ·cp·ΔT with properties at about 10 °C (water 4.19, ethylene glycol 30 % 3.70, propylene glycol 30 % 3.88 kJ/kgK); air capacity from moist air (evaporator with RH via enthalpy, otherwise sensible only). Refrigerant mass flow follows from Q₀ / q₀; heat recovery is modelled as a desuperheater right after the compressor (point 2H). Measured pipe surface temperatures (strap-on sensors) usually read slightly below the fluid temperature, especially on the discharge line.